Supervision Requirements (Text)

NFPA logo
NFPA-2016
24.10.4 - All pathways between a remote area of refuge stations and the central control point shall be monitored for integrity.

24.13.4. - Power Supplies: All control units shall meet the power supply requirements of section 10.6s

10.6.9 Monitoring Integrity of Power Supplies

10.6.9.1 Unless otherwise permitted or required by 10.6.9.1.3 and 10.6.9.1.6 all primary and secondary power supplies shall be monitored for the presence of voltage at the point of connection to the system.

10.6.9.1.1 – Failure of either the primary or secondary power supply shall result in a trouble signal in accordance with section 10.14

10.6.7.2.1 – The secondary power supply (battery back up) shall have sufficient capacity to operate the system under quiescent load (system operating in a nonalarm condition) for a minimum of 24 hours and, at the end of that period, shall be capable of operating all alarm notification appliances used for evacuation or to direct aid to the location of an emergency for 5 minutes.
Communication Supervision
Communication Supervision for 1-10 Analog System
  • Each 2100 Series Call Box comes with built in Communication verification software and failure relay output which can be connected to an addressable fire alarm module or the fire control panel.
Power Supervision


Power Supervision for 1-10 Analog System

Power Supervision requires additional purchase: 2500-PWR24U